Equipment & SystemsQuestion 281 of 521
In a typical motor branch circuit, which sequence correctly lists the components from the supply toward the motor?
a.Branch-circuit short-circuit/ground-fault device, disconnecting means, controller, overload device, motor
b.Motor, overload, controller, disconnect, fuse
c.Overload, motor, controller, disconnect
d.Controller, motor, fuse, disconnect
Explanation
Article 430 arranges the motor circuit as: branch-circuit short-circuit/ground-fault protection, then the disconnecting means, then the controller, then the overload device, then the motor. The other sequences misplace the protective and control elements.
Law Reference: 2023 NEC §430.1Practice all 521 questions free — no signup required.