Equipment & SystemsQuestion 282 of 521
An HVAC nameplate lists MCA = 27.5 A and MOCP = 45 A. What is the minimum ampacity the branch-circuit conductors must have?
a.45 A
b.27.5 A
c.22 A
d.35 A
Explanation
Conductors must have an ampacity at least equal to the MCA (27.5 A); the MOCP (45 A) is the maximum overcurrent device, not the conductor ampacity. Sizing conductors to 45 A would be oversized/incorrect, and 22 A is below the required MCA.
Law Reference: 2023 NEC §440.4Practice all 521 questions free — no signup required.
Related questions on this topic
- For a 100 HP, 460 V motor (FLC 124 A), what minimum branch-circuit conductor ampacity does NEC 430.22 require?
- For the 100 HP, 460 V motor (FLC 124 A), what is the maximum dual-element (time-delay) fuse per Table 430.52 (175%)?
- In a typical motor branch circuit, which sequence correctly lists the components from the supply toward the motor?
- A rooftop A/C unit has one compressor at 30 A rated-load and a condenser fan at 1.5 A. What is the minimum circuit ampacity (MCA), using 125% of the largest motor plus other loads?
- An HVAC nameplate specifies 'Maximum Fuse or HACR Breaker.' What does HACR indicate?
- What is the rated secondary current of a 75 kVA, three-phase transformer with a 208 V secondary?