An HVAC nameplate lists MCA = 27.5 A and MOCP = 45 A. What is the minimum ampacity the branch-circuit conductors must have?

a.45 A
b.27.5 A
c.22 A
d.35 A

Explanation

Conductors must have an ampacity at least equal to the MCA (27.5 A); the MOCP (45 A) is the maximum overcurrent device, not the conductor ampacity. Sizing conductors to 45 A would be oversized/incorrect, and 22 A is below the required MCA.

Law Reference: 2023 NEC §440.4