An HVAC nameplate specifies 'Maximum Fuse or HACR Breaker.' What does HACR indicate?
a.The breaker must be a GFCI type
b.The breaker must be rated for 100% continuous duty
c.Only fuses may be used, not breakers
d.The circuit breaker is rated/listed for heating, air-conditioning, and refrigeration group-motor applications
Explanation
HACR-rated breakers are listed for heating, air-conditioning, and refrigeration equipment with group motor-compressor loads. The nameplate permits either a fuse or an HACR breaker up to the marked value; it does not mandate GFCI or fuses-only.
Law Reference: 2023 NEC §440.22Practice all 521 questions free — no signup required.
Related questions on this topic
- In a typical motor branch circuit, which sequence correctly lists the components from the supply toward the motor?
- An HVAC nameplate lists MCA = 27.5 A and MOCP = 45 A. What is the minimum ampacity the branch-circuit conductors must have?
- A rooftop A/C unit has one compressor at 30 A rated-load and a condenser fan at 1.5 A. What is the minimum circuit ampacity (MCA), using 125% of the largest motor plus other loads?
- What is the rated secondary current of a 75 kVA, three-phase transformer with a 208 V secondary?
- For the 75 kVA transformer with a 208 A secondary, what is the maximum secondary overcurrent protective device using the 125% value of Table 450.3(B)?
- NEC 450.9 requires that transformer ventilation openings be arranged so that they: