Equipment & SystemsQuestion 284 of 521

An HVAC nameplate specifies 'Maximum Fuse or HACR Breaker.' What does HACR indicate?

a.The breaker must be a GFCI type
b.The breaker must be rated for 100% continuous duty
c.Only fuses may be used, not breakers
d.The circuit breaker is rated/listed for heating, air-conditioning, and refrigeration group-motor applications

Explanation

HACR-rated breakers are listed for heating, air-conditioning, and refrigeration equipment with group motor-compressor loads. The nameplate permits either a fuse or an HACR breaker up to the marked value; it does not mandate GFCI or fuses-only.

Law Reference: 2023 NEC §440.22

Practice all 521 questions free — no signup required.