Equipment & SystemsQuestion 285 of 521
What is the rated secondary current of a 75 kVA, three-phase transformer with a 208 V secondary?
a.208 A
b.360 A
c.180 A
d.125 A
Explanation
Three-phase current: I = 75,000 / (1.732 x 208) = 75,000 / 360 = about 208 A. Dividing by 208 V alone (360 A) omits sqrt(3), and the other values use wrong kVA or voltage.
Practice all 521 questions free — no signup required.
Related questions on this topic
- An HVAC nameplate lists MCA = 27.5 A and MOCP = 45 A. What is the minimum ampacity the branch-circuit conductors must have?
- A rooftop A/C unit has one compressor at 30 A rated-load and a condenser fan at 1.5 A. What is the minimum circuit ampacity (MCA), using 125% of the largest motor plus other loads?
- An HVAC nameplate specifies 'Maximum Fuse or HACR Breaker.' What does HACR indicate?
- For the 75 kVA transformer with a 208 A secondary, what is the maximum secondary overcurrent protective device using the 125% value of Table 450.3(B)?
- NEC 450.9 requires that transformer ventilation openings be arranged so that they:
- A feeder supplies three 460 V, three-phase motors: 25 HP (34 A), 15 HP (21 A), and 10 HP (14 A). Per NEC 430.24, what minimum feeder ampacity is required?