A feeder supplies three 460 V, three-phase motors: 25 HP (34 A), 15 HP (21 A), and 10 HP (14 A). Per NEC 430.24, what minimum feeder ampacity is required?

a.69 A
b.86.25 A
c.84 A
d.77.5 A

Explanation

430.24 requires 125% of the largest FLC plus the sum of the rest: (34 x 1.25) + 21 + 14 = 42.5 + 35 = 77.5 A. 69 A omits the 125% factor, 86.25 A applies 125% to all, and 84 A doubles wrongly.

Law Reference: 2023 NEC §430.24