Equipment & SystemsQuestion 287 of 521
NEC 450.9 requires that transformer ventilation openings be arranged so that they:
a.Are always fitted with fans
b.Face downward only
c.Are not blocked by walls or obstructions, allowing required airflow to dissipate heat
d.Are sealed to keep out dust
Explanation
NEC 450.9 requires ventilation so transformers can dissipate full-load losses without exceeding temperature ratings; openings must not be blocked by walls or obstructions. Forced ventilation is not always required, and sealing openings would defeat cooling.
Law Reference: 2023 NEC §450.9Practice all 521 questions free — no signup required.
Related questions on this topic
- An HVAC nameplate specifies 'Maximum Fuse or HACR Breaker.' What does HACR indicate?
- What is the rated secondary current of a 75 kVA, three-phase transformer with a 208 V secondary?
- For the 75 kVA transformer with a 208 A secondary, what is the maximum secondary overcurrent protective device using the 125% value of Table 450.3(B)?
- A feeder supplies three 460 V, three-phase motors: 25 HP (34 A), 15 HP (21 A), and 10 HP (14 A). Per NEC 430.24, what minimum feeder ampacity is required?
- Per NEC 430.62, the maximum feeder overcurrent device for several motors equals the largest branch-circuit protective device rating plus the sum of the other motors' FLCs. If the largest motor's branch device is 90 A and the other motors' FLCs total 35 A, what is the maximum feeder device?
- The equipment grounding conductor for a motor branch circuit is sized based on what, per NEC 250.122?