Planning & EstimatingQuestion 357 of 521
In a dwelling load calculation, what minimum load must be included for the two required small-appliance branch circuits?
a.1,500 VA
b.3,000 VA
c.4,500 VA
d.2,000 VA
Explanation
Each 20 A small-appliance branch circuit is figured at 1,500 VA, and at least two are required, so 2 × 1,500 = 3,000 VA. 1,500 VA covers only one circuit, and 4,500 VA would be three circuits.
Law Reference: 2023 NEC §220.52(A)Practice all 521 questions free — no signup required.
Related questions on this topic
- A one-family dwelling has 2,000 ft² of habitable floor area. Using the standard method, what is the general lighting and general-use receptacle load?
- How much load must be included for the laundry branch circuit in a dwelling load calculation?
- The combined general lighting, small-appliance, and laundry load of a dwelling is 9,000 VA. After applying the standard-method demand factors, what is the net load?
- Using Table 220.55, Column C, what is the demand load for a single 12 kW household electric range?
- A household electric clothes dryer is rated 4.5 kW. What value is used in the service load calculation?
- A dwelling calculated load totals 24,000 VA on a 240 V, single-phase service. What is the minimum service ampacity this load demands?