Using Table 220.55, Column C, what is the demand load for a single 12 kW household electric range?
a.8 kVA
b.12 kVA
c.6.6 kVA
d.10 kVA
Explanation
For one range not over 12 kW, Column C gives a demand of 8 kVA. 12 kVA is the nameplate rating (no demand applied), so it is incorrect.