Planning & EstimatingQuestion 359 of 521
The combined general lighting, small-appliance, and laundry load of a dwelling is 9,000 VA. After applying the standard-method demand factors, what is the net load?
a.9,000 VA
b.3,150 VA
c.4,200 VA
d.5,100 VA
Explanation
The first 3,000 VA is taken at 100% and the remaining 6,000 VA at 35%: 3,000 + (6,000 × 0.35) = 3,000 + 2,100 = 5,100 VA. Applying 35% to the whole amount or forgetting the first block gives the wrong distractor values.
Law Reference: 2023 NEC §220.42Practice all 521 questions free — no signup required.
Related questions on this topic
- A one-family dwelling has 2,000 ft² of habitable floor area. Using the standard method, what is the general lighting and general-use receptacle load?
- In a dwelling load calculation, what minimum load must be included for the two required small-appliance branch circuits?
- How much load must be included for the laundry branch circuit in a dwelling load calculation?
- Using Table 220.55, Column C, what is the demand load for a single 12 kW household electric range?
- A household electric clothes dryer is rated 4.5 kW. What value is used in the service load calculation?
- A dwelling calculated load totals 24,000 VA on a 240 V, single-phase service. What is the minimum service ampacity this load demands?