Services & DistributionQuestion 6 of 521
What is the minimum length that a ground rod electrode must be in contact with the soil?
a.6 ft (1.8 m)
b.8 ft (2.44 m)
c.10 ft (3.0 m)
d.4 ft (1.2 m)
Explanation
Section 250.53(G) requires that a rod be installed so at least 8 ft (2.44 m) of length is in contact with soil. The other lengths do not meet the code minimum for a driven rod electrode.
Law Reference: 2023 NEC §250.53(G)Practice all 521 questions free — no signup required.