The only grounding electrode is a concrete-encased electrode (Ufer). What is the largest copper GEC that must be run to it?

a.4 AWG
b.6 AWG
c.2 AWG
d.1/0 AWG

Explanation

Per 250.66(B), where the GEC connects solely to a concrete-encased electrode, it need not be larger than 4 AWG copper. 6 AWG is the cap only for rod/pipe/plate electrodes; 2 AWG and 1/0 exceed the concrete-encased allowance.

Law Reference: 2023 NEC §250.66(B)