Services & DistributionQuestion 5 of 521

What is the minimum copper EGC for a circuit protected by a 200 A breaker, per Table 250.122?

a.6 AWG
b.8 AWG
c.4 AWG
d.3 AWG

Explanation

Table 250.122 lists 6 AWG copper for a 200 A device. 8 AWG serves only up to 100 A; 4 AWG is for 300 A and 3 AWG for 400 A.

Law Reference: 2023 NEC §250.122