Services & DistributionQuestion 2 of 521

The GEC from a service runs only to a driven ground rod (rod/pipe electrode). What is the largest copper GEC required for this connection?

a.4 AWG
b.2 AWG
c.6 AWG
d.It must match Table 250.66 sizing

Explanation

Per 250.66(A), the portion of the GEC that is the sole connection to a rod, pipe, or plate electrode need not be larger than 6 AWG copper. Table 250.66 sizes larger conductors, but the rod exception caps it at 6 AWG; 4 AWG and 2 AWG exceed what the rod can use.

Law Reference: 2023 NEC §250.66(A)