Gas PipingQuestion 267 of 360
A CSST system is being bonded. Which practice reflects correct bonding technique?
a.Bond the CSST tubing wall at any convenient corrugation with a small wire
b.Attach the bonding clamp to a rigid pipe component or a CSST fitting, using a jumper at least No. 6 AWG copper, connected to the grounding electrode system
c.No bonding connection is ever needed on CSST
d.Use the gas as the grounding path
Explanation
CSST bonding is made to a rigid metallic pipe segment or a CSST fitting, not to the thin corrugated tube wall, using a listed clamp and a jumper of at least No. 6 AWG copper connected to the building grounding electrode system. This diverts electrical energy safely and reduces arc-perforation risk from lightning. Always follow the CSST manufacturer's bonding instructions and the electrical code.
Practice all 360 questions free — no signup required.
Related questions on this topic
- A sizing table (natural gas) shows 1/2-inch pipe carries 92 cfh and 3/4-inch pipe carries 190 cfh at the governing length. A section supplies a 40,000 BTU/hr wall furnace plus a 45,000 BTU/hr water heater. What is the smallest size that works?
- Which installation practice for a flexible appliance connector is correct?
- Why must horizontal and vertical gas piping be supported at the intervals required by code?
- An older flexible connector is found kinked and corroded when a water heater is replaced. What is the correct action?
- Gas piping must pass through a concrete slab. What is the correct approach?
- When sizing gas piping, why does the code sometimes require adding equivalent lengths for fittings such as elbows and tees?