Wiring Methods & MaterialsQuestion 60 of 120
A device box has three 14-2 NM cables with equipment grounding conductors entering through internal clamps, and one single-pole switch is installed. What minimum box volume is required?
a.20.0 cubic inches
b.18.0 cubic inches
c.16.0 cubic inches
d.22.5 cubic inches
Explanation
Six insulated conductors count individually, all equipment grounding conductors together count as one, all internal clamps together count as one, and the switch yoke counts as two, for 10 allowances. At 2.00 cubic inches for 14 AWG, 10 x 2.00 = 20.0 cubic inches. The 18.0 answer misses one allowance, 16.0 omits both the clamp and grounding allowances, and 22.5 uses the 12 AWG allowance by mistake.
Law Reference: 2023 NEC §314.16(B)Practice all 120 questions free — no signup required.
Related questions on this topic
- A box contains six 12 AWG conductors, one internal cable clamp and one duplex receptacle, all 12 AWG. What minimum box volume is required?
- What is the minimum trade size of EMT required for nine 12 AWG THHN conductors?
- When more than two conductors are installed in a raceway, what is the maximum permitted percentage of the raceway cross-sectional area they may occupy?
- A short raceway nipple no longer than 24 inches connects two enclosures. What fill percentage is permitted?
- Four 3/0 AWG THWN conductors, each 0.2679 square inch in area, are pulled into rigid metal conduit. What is the minimum trade size?
- What is the minimum cover for a direct-buried UF cable installed in a residential yard on a 120-volt, 20-ampere circuit that is NOT GFCI protected?
Last reviewed: · editorial process
PrepPass Editorial Team · Verified against Journeyman Electrician Licensing Exam (NEC-based) · How we review