Wiring Methods & MaterialsQuestion 62 of 120
When more than two conductors are installed in a raceway, what is the maximum permitted percentage of the raceway cross-sectional area they may occupy?
a.53 percent
b.31 percent
c.40 percent
d.60 percent
Explanation
Chapter 9, Table 1 allows 53 percent fill for one conductor, 31 percent for exactly two conductors and 40 percent for three or more. The 60 percent value applies only to a nipple not exceeding 24 inches in length between boxes or enclosures.
Law Reference: 2023 NEC Chapter 9, Table 1Practice all 120 questions free — no signup required.