Wiring Methods & MaterialsQuestion 68 of 120
A GFCI-protected 120-volt, 20-ampere residential branch circuit is direct buried in a yard. What is the minimum cover?
a.18 inches
b.6 inches
c.12 inches
d.24 inches
Explanation
Residential branch circuits rated 120 volts or less and 20 amperes or less that have GFCI protection may be buried with only 12 inches of cover, because a ground fault from a dig-in will clear immediately. Without GFCI protection the general 24-inch requirement applies, and the 6- and 18-inch values belong to metal and nonmetallic raceways.
Law Reference: 2023 NEC Table 300.5Practice all 120 questions free — no signup required.
Related questions on this topic
- What is the minimum cover for a direct-buried UF cable installed in a residential yard on a 120-volt, 20-ampere circuit that is NOT GFCI protected?
- What is the minimum burial cover for rigid metal conduit installed underground in a location not otherwise specified?
- What is the minimum burial cover for a nonmetallic raceway listed for direct burial without concrete encasement, installed under a lawn?
- How must electrical metallic tubing be secured and supported on a normal horizontal run?
- How must Type NM cable be supported where it enters a box equipped with cable clamps?
- At what maximum interval must Type MC cable be supported and secured?