Wiring Methods & MaterialsQuestion 70 of 120

How must Type NM cable be supported where it enters a box equipped with cable clamps?

a.Secured within 8 inches of the box and supported every 6 feet
b.Secured within 12 inches of the box and supported at least every 4 and 1/2 feet
c.Secured within 3 feet of the box and supported every 10 feet
d.Secured within 12 inches of the box and supported every 6 feet

Explanation

Type NM cable is secured within 12 inches of each box, cabinet or fitting and supported at intervals not exceeding 4 and 1/2 feet. The 8-inch figure applies to a single-gang nonmetallic box without clamps, the 3-foot and 10-foot values are EMT, and the 6-foot interval belongs to MC cable.

Law Reference: 2023 NEC §334.30