Wiring Methods & MaterialsQuestion 73 of 120
What is the maximum support spacing for a 1-inch trade size rigid PVC conduit?
a.6 feet
b.5 feet
c.3 feet
d.10 feet
Explanation
PVC expands and sags with temperature, so support spacing depends on trade size: one-half through 1 inch is supported every 3 feet, 1 and 1/4 through 2 inch every 5 feet, and larger sizes at progressively longer intervals. The 10-foot spacing belongs to EMT and rigid metal conduit, which are far stiffer.
Law Reference: 2023 NEC §352.30(B)Practice all 120 questions free — no signup required.