Wiring Methods & MaterialsQuestion 76 of 120
A pull box is used for a straight pull, and the largest raceway entering it is 3 inch trade size. What is the minimum required length of the box in the direction of the pull?
a.18 inches
b.24 inches
c.12 inches
d.36 inches
Explanation
For straight pulls, the box length must be at least eight times the trade size of the largest raceway: 8 x 3 = 24 inches. The 18-inch answer uses a factor of six, which applies to angle and U pulls, and 12 inches uses a factor of four that appears nowhere in the rule.
Law Reference: 2023 NEC §314.28(A)(1)Practice all 120 questions free — no signup required.
Related questions on this topic
- What is the maximum support spacing for a 1-inch trade size rigid PVC conduit?
- What is the maximum total amount of bend permitted in one run of EMT between pull points?
- A cable passes through a bored hole in a wood stud. If the edge of the hole is less than 1 and 1/4 inches from the nearest edge of the stud, what is required?
- An angle pull box has one 2-inch raceway and one 1-inch raceway entering the same wall, with conductors turning 90 degrees. What is the minimum distance from that wall to the opposite wall?
- How must liquidtight flexible metal conduit be secured on a normal run?
- How many 12 AWG conductors may be installed in a 4-11/16 inch by 2-1/8 inch square box with a volume of 42.0 cubic inches, assuming no clamps, devices or fittings?
Last reviewed: · editorial process
PrepPass Editorial Team · Verified against Journeyman Electrician Licensing Exam (NEC-based) · How we review