Gas PipingQuestion 93 of 120

A new residential gas piping system will operate at a working pressure of 7 in w.c. (about 1/4 psi). What is the minimum test pressure required for the pressure test?

a.0.375 psi, which is 1.5 times the working pressure
b.3 psi
c.10 psi
d.1.5 in w.c.

Explanation

The test pressure must be at least 1.5 times the proposed maximum working pressure but never less than 3 psi, and 1.5 times 1/4 psi is far below that floor, so 3 psi governs. The 0.375 psi and 1.5 in w.c. answers apply the multiplier while ignoring the 3 psi minimum; 10 psi exceeds what the code requires for this system.

Law Reference: IFGC §406.4

Practice all 120 questions free — no signup required.

Related questions on this topic

Last reviewed: · editorial process

PrepPass Editorial Team · Verified against Journeyman Plumber Licensing Exam (UPC/IPC-based) · How we review