Framing & StructuralCâu 313 / 700

When a pipe notch or bore in a wood stud leaves less than 1-1/4 inch of wood between the pipe and the exposed face, what protection does the code require?

a.A steel plate or shield of adequate thickness over the area to guard against fastener penetration
b.Nothing, provided the pipe is copper
c.Doubling the drywall thickness
d.Filling the notch with expanding foam

Giải thích

Where less than 1-1/4 inch of wood remains between a pipe and the stud face, a steel nail plate (typically at least 16 gauge) must protect the pipe so later nails or screws cannot puncture it. Pipe material, extra drywall, and foam do not stop a driven fastener from reaching the pipe.

Trích dẫn luật: 2025 CA Residential Code §R602.6.1

Luyện miễn phí toàn bộ 700 câu hỏi — không cần đăng ký.

Câu hỏi liên quan cùng chủ đề

Cập nhật gần nhất: · quy trình kiểm tra

Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB General Building (B) Trade Examination · Quy trình kiểm tra
Báo lỗi