Drainage, Waste & VentCâu 3 / 120
Except for traps specifically designed as deep seal traps, what is the required liquid seal depth of a fixture trap?
a.1 in to 2 in
b.1-1/2 in to 3 in
c.2 in to 6 in
d.2 in to 4 in
Giải thích
A standard fixture trap must hold a liquid seal of not less than 2 in and not more than 4 in. Seals shallower than 2 in evaporate or siphon away too easily, and a seal deeper than 4 in is classified as a deep seal trap, which is permitted only in specific applications, so the wider or shallower ranges are incorrect.
Trích dẫn luật: IPC §1002.4Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A horizontal 2 in fixture branch is installed at the code minimum slope. Over a developed run of 18 ft, how much total fall does the pipe have?
- What is the maximum developed length permitted between the trap weir and the vent opening for a 1-1/2 in trap arm?
- A 4 in building drain runs 96 ft from the last fixture connection to the point where it leaves the structure. Installed at the code minimum slope for its size, what is the total fall?
- A fixture drain serving a lavatory is 1-1/2 in in diameter. What is the smallest vent size that may serve it?
- A horizontal building drain changes direction with a fitting that turns the flow 90 degrees. What does the code require at that point?
- A 2 in trap arm serves a floor-mounted fixture. The trap weir is at elevation 0. What is the greatest amount the trap arm may fall before it reaches the vent connection?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với Journeyman Plumber Licensing Exam (UPC/IPC-based) · Quy trình kiểm tra