An 8 in building drain is proposed at 1/16 in per ft over a 200 ft run. What is the fall, and is that slope permitted?
a.6-1/4 in, and the slope is never permitted
b.12-1/2 in, and the slope may be permitted for 8 in and larger pipe where approved
c.25 in, and the slope may be permitted for 8 in and larger pipe where approved
d.50 in, and the slope is never permitted
Giải thích
At 1/16 in per ft, 200 ft x 1/16 in = 12-1/2 in of fall, and slopes as flat as 1/16 in per ft may be approved for pipe 8 in and larger where the resulting velocity is adequate. The 25 in and 50 in figures come from applying the 1/8 in and 1/4 in rates, and 6-1/4 in halves the correct fall.
Luyện miễn phí toàn bộ 120 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A 4 in horizontal drain is sized to carry a load of drainage fixture units. Which pipe run carries the greatest DFU load for a given diameter?
- A branch serves one water closet at 4 DFU, one lavatory at 1 DFU, one bathtub with shower at 2 DFU, and one kitchen sink at 2 DFU. What is the total DFU load on that branch?
- A horizontal fixture branch serves three lavatories only. Any branch that receives the discharge of a water closet must be at least what size?
- A 1-1/4 in trap arm serves a small lavatory. The vent is located 3 ft of developed length from the trap weir. What is the correct evaluation?
- A row of five lavatories on a common horizontal branch in a public restroom is vented by a single vent connected between the last two fixture drains. What type of venting is this?
- A bathroom group is arranged so that the lavatory drain also serves as the vent for the bathtub downstream of it. What is this arrangement called, and what limits it?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với Journeyman Plumber Licensing Exam (UPC/IPC-based) · Quy trình kiểm tra