From the motor full-load current table, what is the full-load current of a 25-HP, 480-V, three-phase induction motor?
a.34 A
b.40 A
c.28 A
d.42 A
Giải thích
The table value for a 25-HP, 460-480-V three-phase motor is 34 A. Table full-load current (FLC), not nameplate, is used for conductor and protection sizing.
Trích dẫn luật: 2023 NEC Table 430.250Luyện miễn phí toàn bộ 110 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- Using the 75 C column, what is the smallest copper conductor rated to carry a 100-A service load?
- For a 200-A dwelling service using the 83% conductor allowance, what is the smallest copper ungrounded conductor (75 C) permitted for the main power feeder?
- An electric range has a Column C demand of 8,000 VA. Using the 70% neutral demand for ranges, what is the range contribution to the feeder neutral load?
- A single continuous-duty motor has a table full-load current of 34 A. What minimum conductor ampacity is required for its branch circuit?
- A motor with a service factor of 1.15 has a nameplate full-load current of 34 A. What is the maximum overload protection setting at 125%?
- For a motor with a 34-A full-load current, what is the maximum inverse-time circuit breaker for branch-circuit short-circuit and ground-fault protection (250%, then next higher standard size)?