What is the full-load secondary current of a 75-kVA, three-phase transformer with a 208-V secondary?
a.156 A
b.180 A
c.208 A
d.90 A
Giải thích
Secondary current = 75,000 / (1.732 x 208) = 208.2 A, about 208 A.
Luyện miễn phí toàn bộ 110 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- For a motor with a 34-A full-load current, what is the maximum inverse-time circuit breaker for branch-circuit short-circuit and ground-fault protection (250%, then next higher standard size)?
- A feeder supplies three motors with full-load currents of 34 A, 28 A, and 22 A. What minimum conductor ampacity is required for the feeder?
- What is the full-load primary current of a 75-kVA, 480-V, three-phase transformer?
- A 75-kVA transformer has a 90-A primary current (over 9 A). With primary-only protection at 125% max, what is the primary overcurrent device rating (next higher standard permitted)?
- A 120-V branch circuit carries 16 A over a one-way run of 80 ft using #12 Cu (circular mils = 6,530, K = 12.9). What is the approximate voltage drop?
- Using the previous circuit (5.06-V drop on a 120-V circuit), what is the approximate percent voltage drop?