Services & DistributionCâu 33 / 110
Where the grounding electrode conductor connects only to a made ground rod, what is the largest copper conductor size ever required?
a.#6 AWG
b.#4 AWG
c.#8 AWG
d.#2 AWG
Giải thích
The portion of the GEC connecting solely to a rod, pipe, or plate electrode need not be larger than #6 Cu.
Trích dẫn luật: 2023 NEC 250.66(A)Luyện miễn phí toàn bộ 110 câu hỏi — không cần đăng ký.