Services & DistributionCâu 42 / 110
A conductor has an allowable ampacity of 115 A, which is not a standard rating. Under the next-standard-size rule (600 A or less), what is the largest permitted overcurrent device?
a.110 A
b.125 A
c.150 A
d.100 A
Giải thích
When ampacity does not match a standard rating and conditions are met, the next higher standard device (125 A) is permitted for 800-A or smaller circuits.
Trích dẫn luật: 2023 NEC 240.4(B)Luyện miễn phí toàn bộ 110 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- Which of the following is the next standard overcurrent device rating above 95 A?
- Absent a specific exception, what is the maximum overcurrent protection for a #12 Cu conductor?
- Absent a specific exception, what is the maximum overcurrent protection for a #10 Cu conductor?
- What is the smallest conductor size generally permitted to be installed in parallel?
- Two paralleled sets of 500-kcmil Cu (75 C, 380 A each) supply one feeder. What is the combined ampacity before adjustment?
- What is the minimum service disconnecting-means rating for a one-family dwelling?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với Master Electrician Licensing Exam (NEC-based) · Quy trình kiểm tra