Advanced WiringCâu 71 / 110
A motor without a marked service factor (or with SF under 1.15) has a full-load current of 28 A. What is the maximum overload protection at 115%?
a.35 A
b.28 A
c.32.2 A
d.30 A
Giải thích
For motors with a service factor less than 1.15, overload protection is limited to 115% of nameplate FLA: 28 x 1.15 = 32.2 A.
Trích dẫn luật: 2023 NEC 430.32(A)Luyện miễn phí toàn bộ 110 câu hỏi — không cần đăng ký.