CalculationsCâu 8 / 110
A dwelling has four fastened-in-place appliances (dishwasher, disposal, water heater, compactor) totaling 6,000 VA. What is the demand load after applying the fastened-appliance demand factor?
a.6,000 VA
b.3,000 VA
c.7,500 VA
d.4,500 VA
Giải thích
Where four or more fastened-in-place appliances are on the same feeder, a 75% demand factor may be applied: 6,000 x 0.75 = 4,500 VA.
Trích dẫn luật: 2023 NEC 220.53Luyện miễn phí toàn bộ 110 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- What is the demand load for two 12-kW household electric ranges served from one feeder (range demand table, Column C, two appliances)?
- A single household range is rated 16 kW. Using the 5% increase per kW over 12 kW rule on the 8-kW base, what is the demand load?
- A dwelling has one 4-kW electric clothes dryer. What value must be used as the dryer demand load in the service calculation?
- A dwelling's total calculated load is 24,000 VA on a 240-V, single-phase service. What is the calculated service current?
- Using the 75 C column, what is the smallest copper conductor rated to carry a 100-A service load?
- For a 200-A dwelling service using the 83% conductor allowance, what is the smallest copper ungrounded conductor (75 C) permitted for the main power feeder?