A 4 in building drain is run at the code minimum slope of 1/8 in per foot over a developed length of 96 ft. What is the total fall from the upstream end to the downstream end?
a.6 in
b.12 in
c.9 in
d.24 in
Giải thích
Fall = slope x length = 1/8 in/ft x 96 ft = 12 in, or 1 ft. Pipe 3 in and larger uses 1/8 in per foot as the minimum. Using 1/4 in per ft (which applies only to pipe 2-1/2 in and smaller) would wrongly double the answer to 24 in.
Trích dẫn luật: IPC §704.1Luyện miễn phí toàn bộ 110 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- Available pressure for friction is 30 psi and the total developed length of the water line is 150 ft. What is the maximum allowable uniform friction loss per 100 ft of pipe (the value used to enter a sizing chart)?
- A horizontal drainage branch carries the following drainage fixture units (DFU): 4 water closets at 4 DFU, 4 lavatories at 1 DFU, and 2 kitchen sinks at 2 DFU. What is the total DFU load carried by the branch?
- A horizontal fixture branch carries 30 DFU. The sizing table lists these branch capacities: 2 in = 6 DFU, 3 in = 20 DFU, 4 in = 160 DFU. Two of the fixtures are water closets. What is the minimum pipe size for the branch?
- A 2 in horizontal fixture drain must fall a total of 5 in over its run at the code minimum slope of 1/4 in per foot. How long is the run?
- A vent must be sized at not less than one-half the diameter of the drain it serves, and never smaller than 1-1/4 in. What is the minimum vent size for a 3 in drain?
- A 2 in trap arm connects a fixture trap to its vent. The code limits the fall in a trap arm to no more than one pipe diameter between the trap weir and the vent. What is the maximum allowable fall in this trap arm?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với Master Plumber Licensing Exam (UPC/IPC-based) · Quy trình kiểm tra