Design & SizingCâu 20 / 110
A storm sizing table is published at 4 in/hr. A vertical leader lists a capacity of 4,600 ft^2 of roof at 4 in/hr. If the local design rate is only 2 in/hr, what roof area can that same leader serve?
a.2,300 ft^2
b.4,600 ft^2
c.18,400 ft^2
d.9,200 ft^2
Giải thích
Capacity in area is inversely proportional to rainfall rate, so halving the rate from 4 to 2 in/hr doubles the allowable area: 4,600 x (4/2) = 9,200 ft^2. Conductor capacity is fixed in gpm, so a lighter storm lets the same pipe drain more roof. Always adjust table areas to the local rainfall rate.
Trích dẫn luật: UPC §1101.0Luyện miễn phí toàn bộ 110 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A gas branch must deliver 55 cfh of natural gas over a 60 ft longest length. The sizing table for that length gives these capacities: 1/2 in = 42 cfh, 3/4 in = 88 cfh, 1 in = 165 cfh. What is the minimum pipe size?
- Using the rational method Q = 0.0104 x A x i, where A is the projected roof area in square feet and i is the rainfall rate in in/hr, what is the design storm flow for a 6,000 ft^2 roof at a 3 in/hr rainfall rate?
- A roof drains 4,800 ft^2 at a design rainfall rate of 4 in/hr. Using Q = 0.0104 x A x i, what is the storm design flow?
- A booster pump must deliver 40 gpm and raise pressure by 45 psi. Using approximate water horsepower WHP = (gpm x psi) / 1,714, what is the water horsepower required (before pump efficiency)?
- A booster pump adds 52 psi. What is the equivalent head, in feet, that the pump develops? Use 1 psi = 2.31 ft of head.
- A recirculation loop must deliver 6 gpm of hot water. Using v = 0.408 x Q / d^2, what inside diameter keeps the velocity at about 2 ft/s to limit erosion of the continuously circulated hot line?