Where the grounding electrode conductor connects only to a concrete-encased electrode, what is the largest size it is required to be?

a.2 AWG copper
b.6 AWG copper
c.4 AWG copper
d.1/0 AWG copper

Explanation

The conductor to a concrete-encased electrode is never required to be larger than 4 AWG copper. The 6 AWG cap belongs to rod, pipe and plate electrodes, and 2 AWG or 1/0 would only come from Table 250.66 before this limiting rule is applied.

Law Reference: 2023 NEC §250.66(B)