What is the minimum size copper equipment grounding conductor for a 400-ampere feeder?

a.4 AWG
b.3 AWG
c.2 AWG
d.1 AWG

Explanation

Table 250.122 lists 3 AWG copper at 400 amperes. 4 AWG is the 300-ampere value, 2 AWG the 500-ampere value and 1 AWG the 600-ampere value, so all three are one row away from the correct entry.

Law Reference: 2023 NEC Table 250.122