A 200-ampere feeder requires what minimum size copper equipment grounding conductor?

a.3 AWG
b.8 AWG
c.4 AWG
d.6 AWG

Explanation

The 200-ampere row of Table 250.122 specifies 6 AWG copper. 8 AWG belongs to 100 amperes, 4 AWG to 300 amperes and 3 AWG to 400 amperes, so those choices come from reading adjacent rows.

Law Reference: 2023 NEC Table 250.122