A device box contains four 12 AWG circuit conductors, two 12 AWG equipment grounding conductors, and one duplex receptacle. Using 2.25 cubic inches per 12 AWG conductor, what MINIMUM box volume is required?
a.About 13.5 cubic inches
b.About 15.75 cubic inches
c.About 18.0 cubic inches
d.About 20.25 cubic inches
Giải thích
Count 4 for the circuit conductors, 1 for all grounding conductors combined, and 2 for the yoke (device) based on the largest conductor, giving 7 units x 2.25 = 15.75 cubic inches. Counting the grounds individually or the device as one raises or lowers the total incorrectly.
Trích dẫn luật: 2025 CA Electrical Code (CEC) §314.16 (Box Fill)Luyện miễn phí toàn bộ 700 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- When 7 current-carrying conductors are bundled together in a single raceway, their allowable ampacity must be adjusted to what percent of the base value?
- In a dwelling, 125-volt receptacles must have GFCI protection when installed within what distance of the outside edge of a kitchen or wet-bar sink?
- Which of the following branch circuits is MOST clearly required to have arc-fault circuit-interrupter (AFCI) protection?
- A 240-volt, 30-ampere dedicated circuit is wired with copper conductors. Under typical residential conditions, what is the MINIMUM copper conductor size that matches this 30-ampere circuit?
- In new dwelling construction, 15- and 20-ampere, 125-volt receptacles installed in normally accessible locations must generally be:
- For a 2-inch fixture drain, what is a common MAXIMUM developed length of the trap arm (from the trap weir to the vent)?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB General Building (B) Trade Examination · Quy trình kiểm tra