A 120-volt lighting circuit runs a long distance and the fixtures at the far end appear dim. The MOST likely electrical cause and its fix is:

a.Too little load; add more fixtures
b.Excessive voltage drop on the long run; use a larger conductor size or shorten the run
c.The breaker is too large; install a smaller breaker
d.The neutral is oversized; reduce its size

Giải thích

Dim fixtures at the end of a long run indicate voltage drop from conductor resistance over distance; the remedy is upsizing the conductor (or reducing length/load) to keep drop within recommended limits, generally about 3 percent for a branch circuit. Adding load worsens drop; breaker and neutral sizing do not cause dimming this way.

Trích dẫn luật: 2025 CA Electrical Code (based on NEC)