Mạch nhánh & Đi dâyCâu 125 / 521
A 125-volt, 20-ampere receptacle installed in the unfinished portion of a dwelling basement used for storage or a work area requires what protection?
a.AFCI only
b.GFCI
c.No protection
d.Isolated ground
Giải thích
Section 210.8(A)(5) requires GFCI protection for receptacles in unfinished basement areas not intended as habitable rooms, such as storage and work areas, because of the damp concrete environment. AFCI alone does not provide shock protection; 'no protection' and an isolated ground do not satisfy the rule.
Trích dẫn luật: 2023 NEC §210.8(A)(5)Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.