Mạch nhánh & Đi dâyCâu 130 / 521
In a dwelling bathroom, at least one receptacle outlet must be installed within what distance of the outside edge of each basin?
a.12 in
b.2 ft
c.3 ft
d.6 ft
Giải thích
Section 210.52(D) requires a receptacle outlet within 3 ft of the outside edge of each bathroom basin. The receptacle must be on a wall or partition adjacent to the basin, or on the countertop/basin cabinet side. 12 in and 2 ft are stricter than required; 6 ft exceeds the code limit.
Trích dẫn luật: 2023 NEC §210.52(D)Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.