Mạch nhánh & Đi dâyCâu 194 / 521
Per Annex C, Table C.1, what is the maximum number of 14 AWG THHN conductors permitted in 1/2" EMT?
a.9
b.12
c.10
d.15
Giải thích
Table C.1 lists 12 for 14 AWG THHN in 1/2" EMT. 9 is the count for 12 AWG, and 10 or 15 are not listed values for this size.
Trích dẫn luật: 2023 NEC Annex C, Table C.1Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- Per Chapter 9, Table 1, what is the maximum permitted fill percentage when exactly two conductors are installed in a conduit?
- Per Chapter 9, Table 1, what is the maximum permitted fill percentage when only one conductor is installed in a conduit?
- Per Annex C, Table C.1, what is the maximum number of 12 AWG THHN conductors permitted in 1/2" EMT?
- Per Annex C, Table C.1, what is the maximum number of 12 AWG THHN conductors permitted in 3/4" EMT?
- Per Annex C, Table C.1, what is the maximum number of 10 AWG THHN conductors permitted in 1/2" EMT?
- The internal cross-sectional area of 1/2" EMT is 0.304 in³ per Table 4. For three or more conductors, what usable fill area (40%) is available?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-10 Electrical Trade Examination · Quy trình kiểm tra