Mạch nhánh & Đi dâyCâu 199 / 521
Given a 40% usable fill area of 0.213 in² (3/4" EMT) and a 12 AWG THHN cross-sectional area of 0.0133 in² (Table 5), how many 12 AWG THHN conductors fit?
a.9
b.12
c.16
d.22
Giải thích
0.213 ÷ 0.0133 = 16.0, so 16 conductors fit — matching Annex C. 9 corresponds to 1/2" EMT, 22 is the 14 AWG count for 3/4", and 12 is not correct here.
Trích dẫn luật: 2023 NEC Chapter 9, Table 4Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- Per Annex C, Table C.1, what is the maximum number of 10 AWG THHN conductors permitted in 1/2" EMT?
- The internal cross-sectional area of 1/2" EMT is 0.304 in³ per Table 4. For three or more conductors, what usable fill area (40%) is available?
- The internal area of 3/4" EMT is 0.533 in² per Table 4. What is the 40% usable fill area for three or more conductors?
- Six current-carrying 12 AWG THHN conductors (90°C, 30 A base) share a raceway. Applying only the adjustment factor for 4–6 conductors, what is the adjusted ampacity?
- Per Table 310.15(C)(1), what adjustment (derating) factor applies when there are 7 to 9 current-carrying conductors in a raceway?
- Per Table 310.15(C)(1), what adjustment factor applies when there are 4 to 6 current-carrying conductors in a raceway?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-10 Electrical Trade Examination · Quy trình kiểm tra