Mạch nhánh & Đi dâyCâu 207 / 521
An 8 AWG THHN copper conductor (55 A at the 90°C column) is installed where the ambient temperature is 46–50°C. Using the 90°C correction factor of 0.82, what is the corrected ampacity?
a.55 A
b.50 A
c.45 A
d.41 A
Giải thích
55 A × 0.82 = 45.1 A, rounded to 45 A. Using no correction (55 A) ignores the elevated ambient, and the other values apply the wrong factor.
Trích dẫn luật: 2023 NEC §310.15(B)Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- In a 3-wire, single-phase circuit (two hots and a neutral), how is the neutral treated when counting current-carrying conductors for adjustment?
- In a 4-wire, 3-phase wye circuit supplying nonlinear (harmonic-producing) loads, how is the neutral treated for conductor-count adjustment?
- Is an equipment grounding conductor (EGC) ever counted as a current-carrying conductor when applying conductor-count adjustment factors?
- Six current-carrying 10 AWG THHN copper conductors (40 A at 90°C) run in a raceway at 40°C ambient. Applying the 0.91 ambient correction and the 0.80 conductor-count adjustment, what is the resulting ampacity?
- For a branch circuit rated 100 A or less, which temperature column must be used for conductor ampacity at the terminations unless the equipment or terminals are listed for a higher temperature?
- A 90°C-rated conductor is terminated on equipment whose lugs are listed for 75°C. Which temperature column limits the conductor's final ampacity at that termination?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-10 Electrical Trade Examination · Quy trình kiểm tra