Per Table 310.16, what is the ampacity of a 12 AWG copper conductor in the 75°C column (before any small-conductor overcurrent limit)?
a.25 A
b.20 A
c.30 A
d.35 A
Giải thích
Table 310.16 lists 25 A for 12 AWG copper at 75°C. 20 A is the 60°C value (and also the 240.4(D) OCPD limit), while 30 A is the 90°C value; 35 A is for 10 AWG.
Trích dẫn luật: 2023 NEC §310.16Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.