A 120 V single-phase circuit uses 12 AWG copper (6,530 cmil) carrying 20 A over a one-way length of 100 ft. Using VD = 2 × K × I × L ÷ cmil with K = 12.9, what is the approximate voltage drop?
a.7.9 V (about 6.6%)
b.3.9 V (about 3.3%)
c.2.0 V (about 1.7%)
d.5.0 V (about 4.2%)
Giải thích
VD = 2 × 12.9 × 20 × 100 ÷ 6,530 = 51,600 ÷ 6,530 ≈ 7.9 V, which is 7.9/120 ≈ 6.6%. The lower values would require either a shorter run or a larger conductor.
Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- Which cable relies on its metal armor together with an internal aluminum bonding strip to serve as the equipment grounding path?
- The NEC informational note recommends that voltage drop on a branch circuit not exceed what percentage of the circuit voltage?
- For the combined feeder plus branch circuit, the NEC informational note recommends total voltage drop not exceed what percentage?
- The circuit in the previous scenario has a voltage drop of about 6.6%, well above the recommended 3% for a branch circuit. What is the most appropriate corrective action?
- A 240 V single-phase circuit uses 10 AWG copper (10,380 cmil) carrying 24 A over a one-way length of 150 ft, with K = 12.9. What is the approximate voltage drop and percentage?
- In the voltage-drop formula for a balanced 3-phase circuit, which multiplier replaces the factor of 2 used in single-phase calculations?