What is the rated primary current of a 25 kVA, single-phase transformer with a 240 V primary?
a.60 A
b.83 A
c.96 A
d.104 A
Giải thích
For a single-phase transformer, I = VA / V = 25,000 / 240 = 104 A. Using 208 V would give 120 A, 300 V gives 83 A, and 416 V gives 60 A; only the correct 240 V yields about 104 A.
Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- If a motor-compressor (rated-load 18 A) will not start on the 175% device, NEC 440.22(A) permits increasing the protection to a maximum of what value?
- A 30 kVA, three-phase transformer has a 480 V primary (primary current ~36 A). With primary-only protection and no supervised condition, what is the maximum primary overcurrent device using the 125% factor of Table 450.3(B)?
- NEC 450.3(B) overcurrent protection percentages for transformers 1000 V or less are based on what?
- A 45 kVA, three-phase transformer has a 208 V secondary. What is the rated secondary current?
- Why must a motor circuit have both overload protection AND short-circuit/ground-fault protection?
- A 30 HP, 460 V, three-phase motor has an FLC of 40 A. What is the minimum ampere rating of the motor disconnecting means (115% of FLC)?