For the 50 HP, 460 V motor (FLC 65 A), what minimum branch-circuit conductor ampacity is required by NEC 430.22?
a.65 A
b.71.5 A
c.74.75 A
d.81.25 A
Giải thích
430.22 requires 125% of FLC: 65 x 1.25 = 81.25 A. 65 A omits the factor, 71.5 A is 110%, and 74.75 A is 115%.
Trích dẫn luật: 2023 NEC §430.22Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- Per NEC Table 430.248, what is the full-load current of a 3 HP, single-phase, 115 V motor?
- For the 3 HP, 115 V single-phase motor (FLC 34 A), what minimum branch-circuit conductor ampacity does NEC 430.22 require?
- Using NEC Table 430.250, what is the full-load current of a 50 HP, 460 V, three-phase motor?
- For the 50 HP, 460 V motor (FLC 65 A), what is the maximum inverse-time circuit breaker per the 250% column of Table 430.52?
- For a continuous-duty three-phase motor rated more than 1 HP without integral overload protection, how many overload units are generally required?
- A continuous-duty motor has a nameplate FLA of 62 A and a service factor of 1.15. What is the maximum overload device rating at 125% under NEC 430.32(A)(1)?