For circuits rated over 800 A, what is the rule for the overcurrent device relative to conductor ampacity?
a.Next higher standard size is allowed
b.It may be twice the ampacity
c.The OCPD rating must not exceed the conductor ampacity
d.There is no limit
Giải thích
Per 240.4(C), where the circuit is over 800 A, the ampacity of the conductors must be equal to or greater than the OCPD rating; the next-size-up allowance of 240.4(B) does not apply. Doubling or 'no limit' are never correct.
Trích dẫn luật: 2023 NEC §240.4(C)Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.