Lập kế hoạch & Dự toánCâu 391 / 521
In a non-dwelling occupancy, 20 general-use receptacle outlets are installed. What load must be included for these receptacles?
a.1,800 VA
b.2,000 VA
c.4,000 VA
d.3,600 VA
Giải thích
Non-dwelling receptacle outlets are calculated at 180 VA each: 20 × 180 = 3,600 VA. Using 90 VA or 100 VA each would produce the smaller distractor values.
Trích dẫn luật: 2023 NEC §220.14(I)Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A dwelling's total calculated load is 44,000 VA on a 240 V service. What is the smallest standard service rating that will carry this load?
- Electric-vehicle supply equipment is considered a continuous load. At what percentage of its rating must the branch circuit and feeder be sized?
- A continuous load (operating 3 hours or more) draws 16 A. What minimum overcurrent-device/conductor rating must serve it?
- A mercantile (store) occupancy has 5,000 ft² of floor area and a general lighting unit load of 3 VA/ft². What is the general lighting load?
- A retail store has 10 linear feet of show-window lighting. Using the show-window unit load, what load must be included?
- For each commercial occupancy accessible to pedestrians, at least one outlet for a sign or outline lighting must be provided with a minimum circuit load of how many VA?