Lập kế hoạch & Dự toánCâu 402 / 521
Using Table 250.66, for copper service-entrance conductors of 3/0 AWG, what is the minimum size copper grounding electrode conductor?
a.6 AWG
b.8 AWG
c.4 AWG
d.2 AWG
Giải thích
Per Table 250.66, service conductors over 2/0 through 3/0 AWG copper require a 4 AWG copper grounding electrode conductor. 8 AWG serves 2 AWG or smaller, and 2 AWG GEC is for larger service conductors.
Trích dẫn luật: 2023 NEC §250.66Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.
Câu hỏi liên quan cùng chủ đề
- A documented, agreed adjustment to the contracted scope of work and price is called what?
- Who typically performs the code-compliance inspections on a permitted electrical project?
- A dwelling's standard-method net calculated load is 28,600 VA on a 240 V service. What is the smallest standard service size that will carry it?
- In a bid, what does overhead refer to?
- Estimators add a waste factor to material quantities to account for what?
- A home run is 60 ft long and pulls 3 conductors. Adding 10% for waste, approximately how much conductor should be ordered?
Cập nhật gần nhất: · quy trình kiểm tra
Đội Ngũ Biên Tập PrepPass · Đối chiếu với California CSLB C-10 Electrical Trade Examination · Quy trình kiểm tra