Dịch vụ & Phân phốiCâu 63 / 521
For a single service, the maximum number of service disconnects permitted for each service permitted by 230.40 is:
a.Two
b.Three
c.Four
d.Six
Giải thích
Section 230.71 permits up to six service disconnects for each service; in the 2023 NEC each must be in a separate enclosure, or be part of listed switchgear/switchboard/metering assemblies. The lower numbers are not the code limit.
Trích dẫn luật: 2023 NEC §230.71Luyện miễn phí toàn bộ 521 câu hỏi — không cần đăng ký.